Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display updated certificate in machine room. 11/19/2020
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No Door restrictor not working. 7/22/2019
A17.1-1996 : Elevators 1.14 - Ventilation 204.3c Yes No Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required 10/10/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - No No Repair broken fire hat light on 1st floor hall button. 8/11/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair inoperative emergency phone. Re-inspection required 10/10/2022
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.3.1.3(m) No No Replace missing cover on electrical box at bottom of elevator hoistway. 12/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need a maintenance control program on site posted on controller 11/19/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room, 11/19/2020
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No The in car fire service visual signal light has been pushed out of the car operating panel and is no longer visible, needs repaired. Re-inspection required 11/4/2025