ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
All emergency fire service features shall be tested, including smoke detectors, heat detectors, and shunt trip disconnect.
|
10/5/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate.
|
8/26/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide MCP.
|
8/26/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
3/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
4/16/2021
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Complete fire service recall on smoke detectors, shunt trips, and heat detectors.
|
9/20/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Label disconnects with feeder panel, location, number, and breaker numbers.
|
9/20/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Seal all penetrations and voids in the hoistway.
|
9/20/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Need to test emergency light.
|
9/20/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Machine room railing system shall be completed.
|
9/20/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Flooring in the cab shall be installed.
|
9/20/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Need pit lighting, light switch, caution signage, and pit door signage.
|
9/20/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
A code compliant fire extinguisher is required in the machine room.
|
9/20/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Need to test emergency alarm and phone.
|
9/20/2018
|