Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)1 Repair loose sight guard at floor 3. 2/25/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 A temporary “dog house” structure has been installed on top of the elevator car to allow the transportation of construction materials. This structure shall either be removed or a permanent structure be constructed to meet code requirements for clearances and size openings. This was sited on a previous inspection.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Phone does not work on battery back-up power. 2/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair emergency light. 2/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light and phone do not work. 4/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Repair car emergency lights. 2/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x There is a substantial gap between the rear elevator car door jamb and the rear car door when the car door is closed. Readjust door to properly close with no gap allowing access to the hoistway. This was sited on a previous report.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Clean elevator car top. 2/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
MO Minimum : Elevators (H) - Machine Rooms (H)3 Cover hole in machine room floor by #1
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) A machine room lighting fixture was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
MO Minimum : Elevators (I) - Pits (I)1 Clean elevator pit. 2/25/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair elevator pit light. 2/25/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit light. 2/25/2021
MO Minimum : Elevators (I) - Pits (I)8 The sump pump hole in the pit shall be provided with a noncombustible cover that is flush with the pit floor. There is currently no cover provided. This was sited on a previous report.
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 The cross head data plate does not have any information filled in to determine weight, capacity and speed.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x 2.11.3a(1) The elevator rear car door opens when phase I is activated. There is no rear landing and so when the rear door is open it is exposed to the hoistway. Clearance between the open car door is not excessive negating the need to remove the elevator from service at this time. Reprogramming and reinspection is required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. This was sited on a previous report.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
conversion conversion n/a Install code data plate. 2/25/2021