Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Install code data plate.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Clean elevator car top.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit light.
MO Minimum : Elevators (A) - Hoistways (A)1 Replace hoistway door sight guards at floor 11.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit light.
MO Minimum : Elevators (A) - Hoistways (A)1 Replace hoistway door sight guards at floor 11. Initially sited on 2/20.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean elevator car top. Initially sited on 5/19.
MO Minimum : Elevators (A) - Hoistways (A)1 Replace hoistway door sight guards at floor 11. Initially sited on 2/20.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean elevator car top. Initially sited on 5/19.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
conversion conversion conversion - reinspect x replace hoist ropes reaching maximum stretch and rouge (30 days). 5/1/2019
conversion conversion conversion - reinspect x emergency phone not working and bell not working on battery power. 5/1/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Suspension ropes are well below minimum diameter and rouged. Elevator taken out of service. 5/24/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light and alarm inoperative. 2/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone inoperative on battery back-up power. 2/22/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm bell does not work on 110v emergency power. Repair or replace 4/7/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire recall phase one and two shall be tested. Also both buffers and car safeties remain to be tested 7/28/2023
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.20.10 x x Car failed to lower and hold 125%. 9/13/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Provide testing of Phase I operations, record results. 9/13/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Provide testing of Phase II operations, record results. 9/13/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm is not working. Re-inspection required 4/4/2024