Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.20.10 x x Car failed to lower and hold 125%. 9/13/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 5/21/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
conversion conversion conversion - reinspect x emergency phone not working and bell not working on battery power. 5/1/2019
conversion conversion n/a Install code data plate.
conversion conversion conversion - reinspect x replace hoist ropes reaching maximum stretch and rouge (30 days). 5/1/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Clean elevator car top.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean elevator car top. Initially sited on 5/19.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean elevator car top. Initially sited on 5/19.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm bell does not work on 110v emergency power. Repair or replace 4/7/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm is not working. Re-inspection required 4/4/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light and alarm inoperative. 2/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone inoperative on battery back-up power. 2/22/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire recall phase one and two shall be tested. Also both buffers and car safeties remain to be tested 7/28/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Provide testing of Phase I operations, record results. 9/13/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Provide testing of Phase II operations, record results. 9/13/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit light.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit light.
MO Minimum : Elevators (A) - Hoistways (A)1 Replace hoistway door sight guards at floor 11.
MO Minimum : Elevators (A) - Hoistways (A)1 Replace hoistway door sight guards at floor 11. Initially sited on 2/20.
MO Minimum : Elevators (A) - Hoistways (A)1 Replace hoistway door sight guards at floor 11. Initially sited on 2/20.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Suspension ropes are well below minimum diameter and rouged. Elevator taken out of service. 5/24/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The sway guides for the elevator weight compensation chains are worn past their service life and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required.