conversion
|
conversion
|
n/a
|
|
|
Install code data plate.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Clean elevator car top.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Repair pit light.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Replace hoistway door sight guards at floor 11.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Repair pit light.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Replace hoistway door sight guards at floor 11. Initially sited on 2/20.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean elevator car top. Initially sited on 5/19.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Replace hoistway door sight guards at floor 11. Initially sited on 2/20.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean elevator car top. Initially sited on 5/19.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell does not work on 110v emergency power. Repair or replace
|
4/7/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire recall phase one and two shall be tested. Also both buffers and car safeties remain to be tested
|
7/28/2023
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.6.4.20.10
|
x
|
x
|
Car failed to lower and hold 125%.
|
9/13/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Provide testing of Phase I operations, record results.
|
9/13/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Provide testing of Phase II operations, record results.
|
9/13/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm is not working. Re-inspection required
|
4/4/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light and alarm inoperative.
|
2/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone inoperative on battery back-up power.
|
2/22/2021
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Suspension ropes are well below minimum diameter and rouged. Elevator taken out of service.
|
5/24/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
replace hoist ropes reaching maximum stretch and rouge (30 days).
|
5/1/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
emergency phone not working and bell not working on battery power.
|
5/1/2019
|