A17.1-1996 : Moving Walks
|
9.3 - Handrails
|
902.4
|
|
|
Both handrails have cracks. Replace
|
|
A17.1-1996 : Moving Walks
|
9.5 - Lighting
|
906.2
|
|
|
Demarcation lights on both ends are out.
|
|
A17.1-1996 : Moving Walks
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Certificate
|
|
|
Display updated certificate in machine room.
|
|
A17.1-1996 : Moving Walks
|
9.7 - Combplates
|
902.8
|
|
|
Replace two upper comb sections within 30 days.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
7.3 - Handrails
|
8.6.9.1
|
|
|
Right handrail is cracked. Replace.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.3 - Handrails
|
8.11.4.2.13
|
|
|
Left handrail has multiple cracks, must be replaced
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.5 - Lighting
|
8.6.11.5(i) Demarcation Lighting Moving Walk (Re-Inspection)
|
x
|
|
Demarcation lights on controller side need to be replaced. Re-inspection required
|
1/8/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
CSR 40-5.100 State Operating Certificate
|
5.100 Display of Certificate
|
|
|
A copy of the current state operating certificate shall be on display in the machine room
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Moving Walks
|
9.5 - Lighting
|
8.6.11.5(i) Demarcation Lighting Moving Walk (Re-Inspection)
|
x
|
|
Demarcation lights on controller side need replaced
|
|
Missouri Minimum : Moving Walks
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) display of certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
Missouri Minimum : Moving Walks
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.9.1 Moving Walk Handrails
|
|
|
Left handrail has cracks, needs to be replaced
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Bolt on brake is stripped, unable to check brake torque, need to replace bolt
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Brake torque needs to be tested. Re-inspection required
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Brake torque shall be tested, inspection team was unable to check the brake torque. Re-inspection required
|
1/8/2024
|