Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide two-way, hands free, communication inside car. 7/3/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x x Add latching circuitry to elevator controller for fire recall. Did not red tag unit. Reinspect only. 7/3/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Machine space should not be used for storage. 11/17/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Expired
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) No pit bucket. 12/15/2022
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) Terminate/remove scavenger lines returning to the tank. 12/15/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Observed sump pump not plugged in. Determine if unit works, replace if needed.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Observed sump pump not plugged in, in pit. SECOND NOTICE
conversion conversion conversion - reinspect x test and seal ruputure valve 8/28/2018
conversion conversion conversion - reinspect x cover hole in hositway above lower landing to maintain a on hour fire ratin 8/28/2018
conversion conversion conversion - reinspect x provide two way comunication in car, hands free phone 8/28/2018
conversion conversion conversion - reinspect x Install low pressure switch on hydraulic system high pressure side 8/28/2018
conversion conversion conversion - reinspect x Add latching circuitry to elevator controller for fire recall 8/28/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Cab floor has broken floor tiles, a tripping hazard. Repair as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Repair inoperative in car phase I visual indicator.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current certificate.