A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
11/16/2020
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
A17.1 - 8.6.5.16.5 OVER SPEED VALVE NOT SEALED (PERFORM REQUIRED 5 YR OSV TESTING WITHIN 90 DAYS, PER MISSOURI DEPARTMENT OF FIRE SAFETY/ ELEVATOR SAFETY DIVISION, SCHEDULE WITH SCHINDLER.
|
11/15/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(1)
|
|
|
A17.1 8.6.1.4.1(c)(1) A record of oil usage (8.6.5.7). PROVIDE OIL USAGE LOG. BY SCHINDLER
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(3)
|
|
|
A17.1 8.6.1.4.1(c)(3) Periodic tests (see 8.6.1.7) shall be documented or recorded in accordance with 8.6.1.7.2. PROVIDE TEST LOG BY SCHINDLER
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.2 Callbacks (Trouble Calls) Documentation
|
|
|
A17.1 8.6.1.4.2 Callbacks (Trouble Calls). A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. PROVIDE CALLBACK LOG BY SCHINDLER
|
|