Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to check hoistway doors, car & counterweight buffers need to be tested, car & counterweight governors need to be tested. Re-inspection required 1/27/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Machine space illumination is less than 19 fc, due to 2 light fixtures are not working.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Clean the pit.
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) Clean the car top.
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power. 1/14/2025
A17.1-2016 : Elevators 4.12 - Standby power selection switch 2.27.2 Provide testing of the elevator emergency power selector switch (located in the fire control room).
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable, would not connect to the security office. Re-inspection required 1/27/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work properly.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room