MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete, need to check hoistway doors, car & counterweight buffers need to be tested, car & counterweight governors need to be tested. Re-inspection required
|
1/27/2025
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Machine space illumination is less than 19 fc, due to 2 light fixtures are not working.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean the pit.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2c (Clean Car Tops)
|
|
|
Clean the car top.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide testing of the elevator on emergency power.
|
1/14/2025
|
A17.1-2016 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
|
|
Provide testing of the elevator emergency power selector switch (located in the fire control room).
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable, would not connect to the security office. Re-inspection required
|
1/27/2025
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work properly.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|