A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
The battery lowering device is dead. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10.
|
6/7/2022
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
The auxiliary power lowering operation shall be functional.
|
6/6/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
|
4/9/2021
|
A17.1-1996 : Elevators
|
2.37 - Pressure Switch
|
306.14
|
x
|
|
The pressure switch shall be activated by the loss of positive pressure at the top of the cylinder. The pressure switch is not working and shall be repaired or replaced.
|
6/6/2024
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
3/20/2025
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/20/2025
|