Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x The battery lowering device is dead. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. 6/7/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The auxiliary power lowering operation shall be functional. 6/6/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 4/9/2021
A17.1-1996 : Elevators 2.37 - Pressure Switch 306.14 x The pressure switch shall be activated by the loss of positive pressure at the top of the cylinder. The pressure switch is not working and shall be repaired or replaced. 6/6/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 3/20/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/20/2025