Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/20/2025
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) No No Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 3/20/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 4/9/2021
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No The battery lowering device is dead. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. 6/7/2022
A17.1-1996 : Elevators 2.37 - Pressure Switch 306.14 Yes No The pressure switch shall be activated by the loss of positive pressure at the top of the cylinder. The pressure switch is not working and shall be repaired or replaced. 6/6/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No The auxiliary power lowering operation shall be functional. 6/6/2024