ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.2.7
|
x
|
|
Elevators connected to a standby or emergency generator shall be tested for operation on standby or emergency power. Re-inspection required
|
1/21/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Perform the following tests to complete Cat 5 full load test: Test drive machine brake with 125% of rated load, test unintended movement function with 125% of rated load, test car safeties at rated speed with rated load, test car buffer at rated speed with rated load, test counterweight buffer at rated speed. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection)
|
x
|
|
Suspension ropes are below minimum diameter, replace suspension ropes. Re-inspection in 30 days
|
11/15/2022
|