Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x Elevators connected to a standby or emergency generator shall be tested for operation on standby or emergency power. Re-inspection required 1/21/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform the following tests to complete Cat 5 full load test: Test drive machine brake with 125% of rated load, test unintended movement function with 125% of rated load, test car safeties at rated speed with rated load, test car buffer at rated speed with rated load, test counterweight buffer at rated speed. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) x Suspension ropes are below minimum diameter, replace suspension ropes. Re-inspection in 30 days 11/15/2022