A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.6.4.20.11 (Re-Inspection)
|
x
|
|
Provide emergency brake for ascending car and unintended motion protection
|
5/22/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection)
|
x
|
|
Provide firefighter cabinet on car operating panel
|
5/22/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Post emergency evacuation of passengers procedure in machine room
|
3/4/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Test and log firefighter operation monthly
|
3/4/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.14 - Code data plate
|
8.9
|
|
|
Provide code data plate and display on disconnect or controller.
|
9/16/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
Maintenance record log not up to date
|
9/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current state operating certificate not displayed
|
9/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.14 - Code data plate
|
8.9
|
|
|
Need to provide code data plate and display on disconnect or controller.
|
8/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
Machine room light fixture is extremly dim. Need to provide a minimum of 10 ft candles of illumination at machine room floor.
|
8/15/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not call out.
|
5/13/2022
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.6.4.20.11 (Re-Inspection)
|
x
|
|
Provide emergency brake for ascending car and unintended motion protection.
|
5/13/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection)
|
|
|
Provide firefighter cabinet on car operating panel
|
5/13/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair the emergency phone.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Repair the pit light.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove the water from the pit.
|
|