Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate not displayed 9/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not call out. 5/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Machine room light fixture is extremly dim. Need to provide a minimum of 10 ft candles of illumination at machine room floor. 8/15/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Maintenance record log not up to date 9/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.9 Need to provide code data plate and display on disconnect or controller. 8/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers procedure in machine room 3/4/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.9 Provide code data plate and display on disconnect or controller. 9/16/2022
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.20.11 (Re-Inspection) x Provide emergency brake for ascending car and unintended motion protection 5/22/2023
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.20.11 (Re-Inspection) x Provide emergency brake for ascending car and unintended motion protection. 5/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) Provide firefighter cabinet on car operating panel 5/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x Provide firefighter cabinet on car operating panel 5/22/2023
MO Minimum : Elevators (I) - Pits (I)1 Remove the water from the pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair the emergency phone.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair the pit light.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Test and log firefighter operation monthly 3/4/2023