Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect Yes No Repair or replace governor to ensure that all moving parts operate freely. 6/1/2018
conversion conversion n/a No No Alarm button does not actuate emergency alarm bell. 1/17/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Test and log firefighter operation monthly
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) No No Provide firefighter phase 2 operation panel cabinet on car operating panel
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Elevator does not recall to designated landing when phase 1 keyswitch is keyed to on.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Elevator does not recall to fire designated landing when phase 1 key switch is activated to on position. 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No Provide new pit ladder. Existing pit ladder is rusted through.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches No No Hoistway access switches do not function
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems Yes No Bottom landing sill to be maintained flush and level with floor surface of landing 12/28/2021
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 No Yes Provide unintended car movement protection.
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.1 No Yes Provide ascending car overspeed protection
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No No maintenance records on site
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.29 - Car and counterweight safeties 8.11.2.3.1 Yes Yes Need to perform safety test with rated load on the car 12/28/2021
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.20.4 Yes No Install a seal on brake tension adjustment along with a metal tag identifying the firm that installed the seal. 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.3.4 Yes No Brake will not stop and hold 125% of rated load. Brake linkage can not be adjusted due to chemical corrosion. Brake linkage needs replacement. 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.9 No No Provide code data plate on disconnect or controller 9/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 Yes Yes Governor tripping speed exceeds maximum allowable tripping speed. Governor linkage is corroded. 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) No No Machine room door does not open from inside machine room.
A17.1-2016 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(1) Electric elevator, dumbwaiter, or material lift Placed out of Service Yes Yes Elevator has been decommissioned
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 2.11.11.1 No No Bottom landing entrance sill is not flush with landing floor. Fill 1 inch gap between landing and entrance sill