ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
Machine room door does not open from inside machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Provide new pit ladder. Existing pit ladder is rusted through.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Elevator does not recall to designated landing when phase 1 keyswitch is keyed to on.
|
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
2.19.1
|
|
x
|
Provide ascending car overspeed protection
|
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
2.19.2
|
|
x
|
Provide unintended car movement protection.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection)
|
|
|
Provide firefighter phase 2 operation panel cabinet on car operating panel
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
Hoistway access switches do not function
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Test and log firefighter operation monthly
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No maintenance records on site
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
|
|
Bottom landing entrance sill is not flush with landing floor. Fill 1 inch gap between landing and entrance sill
|
|
A17.1-2016 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(b)(1) Electric elevator, dumbwaiter, or material lift Placed out of Service
|
x
|
x
|
Elevator has been decommissioned
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Repair or replace governor to ensure that all moving parts operate freely.
|
6/1/2018
|
conversion
|
conversion
|
n/a
|
|
|
Alarm button does not actuate emergency alarm bell.
|
1/17/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13 Door Systems
|
x
|
|
Bottom landing sill to be maintained flush and level with floor surface of landing
|
12/28/2021
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.6.4.20.4
|
x
|
|
Install a seal on brake tension adjustment along with a metal tag identifying the firm that installed the seal.
|
12/28/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Elevator does not recall to fire designated landing when phase 1 key switch is activated to on position.
|
12/28/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.18
|
x
|
x
|
Governor tripping speed exceeds maximum allowable tripping speed. Governor linkage is corroded.
|
12/28/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
8.11.2.3.4
|
x
|
|
Brake will not stop and hold 125% of rated load. Brake linkage can not be adjusted due to chemical corrosion. Brake linkage needs replacement.
|
12/28/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.29 - Car and counterweight safeties
|
8.11.2.3.1
|
x
|
x
|
Need to perform safety test with rated load on the car
|
12/28/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.14 - Code data plate
|
8.9
|
|
|
Provide code data plate on disconnect or controller
|
9/16/2022
|