Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Alarm button does not actuate emergency alarm bell. 1/17/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 2.11.11.1 Bottom landing entrance sill is not flush with landing floor. Fill 1 inch gap between landing and entrance sill
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Bottom landing sill to be maintained flush and level with floor surface of landing 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.3.4 x Brake will not stop and hold 125% of rated load. Brake linkage can not be adjusted due to chemical corrosion. Brake linkage needs replacement. 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Elevator does not recall to designated landing when phase 1 keyswitch is keyed to on.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Elevator does not recall to fire designated landing when phase 1 key switch is activated to on position. 12/28/2021
A17.1-2016 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(1) Electric elevator, dumbwaiter, or material lift Placed out of Service x x Elevator has been decommissioned
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 x x Governor tripping speed exceeds maximum allowable tripping speed. Governor linkage is corroded. 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches Hoistway access switches do not function
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.20.4 x Install a seal on brake tension adjustment along with a metal tag identifying the firm that installed the seal. 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) Machine room door does not open from inside machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.29 - Car and counterweight safeties 8.11.2.3.1 x x Need to perform safety test with rated load on the car 12/28/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No maintenance records on site
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.1 x Provide ascending car overspeed protection
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.9 Provide code data plate on disconnect or controller 9/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) Provide firefighter phase 2 operation panel cabinet on car operating panel
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Provide new pit ladder. Existing pit ladder is rusted through.
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 x Provide unintended car movement protection.
conversion conversion conversion - reinspect x Repair or replace governor to ensure that all moving parts operate freely. 6/1/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Test and log firefighter operation monthly