Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No MCP in machine room
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Maintenance records not up to date.
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake x Emergency brake is not working properly 12/3/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate not displayed
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit x replace defective pit ladder. 9/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.9 - Guarding of exposed auxiliary equipment 2.10.1 hoist ropes need to be guarded to machine room floor where the ropes extend past the base of the driving machine
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone does not operate 5/11/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not call out 5/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Test and log firefighter operation monthly 3/4/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers procedure in machine room 3/4/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) Provide firefighter operation cabinet on car operating panel 5/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x Provide firefighter cabinet on car operating panel 5/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) Top of car light does not illuminate
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Machine room air conditioner does not operate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit x Replace pit ladder. Existing ladder is not usable due to corrosion from water damage. 5/23/2023
conversion conversion n/a Repair pit light. m Pit light does not illuminate. 1/9/2019
conversion conversion n/a Emergency phone inside elavator does not operate. 1/9/2019
conversion conversion n/a Need to install light switch near machine room access door to operate machine room light fixture. Machine light does not illuminate. 1/9/2019
conversion conversion n/a Remove standing water from pit. Summp pump not operating. 1/9/2019