Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) Top of car light does not illuminate
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Test and log firefighter operation monthly 3/4/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit x Replace pit ladder. Existing ladder is not usable due to corrosion from water damage. 5/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit x replace defective pit ladder. 9/6/2023
conversion conversion n/a Repair pit light. m Pit light does not illuminate. 1/9/2019
conversion conversion n/a Remove standing water from pit. Summp pump not operating. 1/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) Provide firefighter operation cabinet on car operating panel 5/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x Provide firefighter cabinet on car operating panel 5/23/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers procedure in machine room 3/4/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone does not operate 5/11/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No MCP in machine room
conversion conversion n/a Need to install light switch near machine room access door to operate machine room light fixture. Machine light does not illuminate. 1/9/2019
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Maintenance records not up to date.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Machine room air conditioner does not operate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.9 - Guarding of exposed auxiliary equipment 2.10.1 hoist ropes need to be guarded to machine room floor where the ropes extend past the base of the driving machine
conversion conversion n/a Emergency phone inside elavator does not operate. 1/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not call out 5/16/2022
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake x Emergency brake is not working properly 12/3/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate not displayed