MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 full load test is incomplete. Need to perform the following tests: traction machine brake with 125% of rated load. Unintended car movement with 125% of rated load. Car safeties at rated speed with rated load. Car buffer at rated speed with rated load. Counterweight buffer at rated speed with no load. Re-inspection required 12/6/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 full load test was never completed from 12/21/23. Need to perform the following tests to complete CAt 5 full load test: Test drive machine brake with 125% of rated load, perform unintended movement test with 125% of rated load, test car safeties with rated load at rated speed, test car buffer at rated speed with rated load, test counterweight buffer at rated speed. Re-inspection required
A17.1-2016 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.6.4.19.17 Earthquake Operation x Counterweight seismic displacement device does not work, needs repaired. Re-inspection required 12/6/2024