conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phone in Elevator cab does not work. (microphone does not work, speaker does)
|
2/20/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV in pit is not sealed. Perform required testing, seal & tag within 90 days. Re-inspection required
|
11/1/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car appears to have no live lie, needs repair. Re-inspection required
|
11/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean dead bat(s) and feces from cartop to provide a safe workspace for elevator personnel
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean pit of dead bats & feces to provide a safe workspace for elevator personnel.
|
|