Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 The heat detector that activates the shunt trip has become detached from its mount and shall be resecured. 4/28/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 4/28/2020
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. 4/28/2020