Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Top floor landing is located outside in a parking garage. The top floor heat detector that actuates phase 1 fire recall at this landing was located below an awning. The old awning was removed and a new awning was installed below the heat detector. This will prevent phase i fire recall in the event of a fire at this landing. Also, the heat detector is now exposed to rain and snow. Either re-install awning above heat detector or relocate the heat detector below the awning. If heat detector is moved, a permit is required. Re-inspection required
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Remove fluid from sump hole and confirm sump is working properly. Clean pit. 11/2/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Cab ceiling panels are open egg crate type providing no protection for passengers in event of breakage. Replace panels with solid type or install plastic tubes & end caps over light bulbs 12/16/2021
MO Minimum : Elevators 2.3 - Lighting and receptacles 110.27 Guarding of Live Parts NFPA 72 No No Cab lighting shall have not less than 2 lamps. Replace missing lamp 12/16/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current state operating certificate shall be properly displayed in machine room 12/16/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Car lighting shall not be less than 2 lamps 12/16/2021