Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Remove fluid from sump hole and confirm sump is working properly. Clean pit. 11/2/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Cab ceiling panels are open egg crate type providing no protection for passengers in event of breakage. Replace panels with solid type or install plastic tubes & end caps over light bulbs 12/16/2021
MO Minimum : Elevators 2.3 - Lighting and receptacles 110.27 Guarding of Live Parts NFPA 72 Cab lighting shall have not less than 2 lamps. Replace missing lamp 12/16/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate shall be properly displayed in machine room 12/16/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Car lighting shall not be less than 2 lamps 12/16/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Top floor landing is located outside in a parking garage. The top floor heat detector that actuates phase 1 fire recall at this landing was located below an awning. The old awning was removed and a new awning was installed below the heat detector. This will prevent phase i fire recall in the event of a fire at this landing. Also, the heat detector is now exposed to rain and snow. Either re-install awning above heat detector or relocate the heat detector below the awning. If heat detector is moved, a permit is required. Re-inspection required