A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Remove fluid from sump hole and confirm sump is working properly. Clean pit.
|
11/2/2021
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Cab ceiling panels are open egg crate type providing no protection for passengers in event of breakage. Replace panels with solid type or install plastic tubes & end caps over light bulbs
|
12/16/2021
|
|
MO Minimum : Elevators
|
2.3 - Lighting and receptacles
|
110.27 Guarding of Live Parts NFPA 72
|
|
|
Cab lighting shall have not less than 2 lamps. Replace missing lamp
|
12/16/2021
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current state operating certificate shall be properly displayed in machine room
|
12/16/2021
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Car lighting shall not be less than 2 lamps
|
12/16/2021
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Top floor landing is located outside in a parking garage. The top floor heat detector that actuates phase 1 fire recall at this landing was located below an awning. The old awning was removed and a new awning was installed below the heat detector. This will prevent phase i fire recall in the event of a fire at this landing. Also, the heat detector is now exposed to rain and snow. Either re-install awning above heat detector or relocate the heat detector below the awning. If heat detector is moved, a permit is required. Re-inspection required
|
|