Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The hall call box located on the 1st floor landing is pulling away from the wall. Take corrective action as needed. 9/15/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Each floor shall have "In Case of Fire Use Stairs" signage. 11/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates "In Case of Fire" signage is required at each floor. (On order per building contact) 12/7/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall be operational. 9/5/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational and code compliant. 11/15/2022
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 1001.2(b)(11) The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 9/15/2021
A17.1-1996 : Elevators 2.14 - Code data plate 1200.6 Install a code data plate. It shall read: A17.1-1996 9/15/2021
A17.1-1996 : Elevators 2.37 Pressure switch 306.14 Pressure switch x Where the top of the cylinder is installed above the top of the storage tank, a pressure switch shall be provided according to A17.1 - 3.26.8 11/20/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 9/15/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 9/15/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 11/22/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean the pit of oil, dirt, and debris. 9/15/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/22/2022