Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Bulbs and tubes in car shall be guarded or sleeved to prevent breakage
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6 6/2/2022
MO Minimum : Elevators (I) - Pits (I)1 Trash and debris in Pit. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. 6/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Light and Bell do not work when normal power is removed 11/16/2023