MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
x
|
|
The battery back–up lowering device could not be tested to verify that it operate as designed. The controller test feature malfunctioned and required repair. Reinspection required
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established from either operator error or programming error. Check and repair the programming of this phone for proper operation and passenger safety so two-way communication can be established. Reinspection required.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher is out of date and needs to be charged
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7
|
|
|
The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency phone not working
|
1/8/2019
|
conversion
|
conversion
|
n/a
|
|
|
Up to date Certificate in machine room
|
1/8/2019
|