Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Up to date Certificate in machine room 1/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher is out of date and needs to be charged
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established from either operator error or programming error. Check and repair the programming of this phone for proper operation and passenger safety so two-way communication can be established. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x The battery back–up lowering device could not be tested to verify that it operate as designed. The controller test feature malfunctioned and required repair. Reinspection required
conversion conversion conversion - reinspect x Emergency phone not working 1/8/2019