Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Emergency phone not working 1/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher is out of date and needs to be charged
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x The battery back–up lowering device could not be tested to verify that it operate as designed. The controller test feature malfunctioned and required repair. Reinspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established from either operator error or programming error. Check and repair the programming of this phone for proper operation and passenger safety so two-way communication can be established. Reinspection required.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
conversion conversion n/a Up to date Certificate in machine room 1/8/2019