ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
The machine room GFCI receptacle was not operational on the day of inspection. Repair the receptacle for maintenance and emergency personnel.
|
10/16/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.
|
10/16/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The elevator pit floor is covered in saturated oil dry. The elevator pit shall be kept clean and dry.
|
10/16/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
A light fixture inside the elevator is not operational and shall be repaired.
|
10/16/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.1 - Door Re-opening device
|
8.6.4.13.1(c) Door Reopening Devices
|
|
|
Repair front door safety edge.
|
7/20/2021
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
OSV is not sealed and must have a cat 5 weight weight test performed within 90 days or less
|
11/17/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
110 disconnect rusting through, shall be replaced
|
9/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
110 disconnect rusting through, needs to be replaced
|
9/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
110 disconnect is rusting through, needs to be replaced
|
9/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
9/20/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19
|
x
|
x
|
Pipe coming out of machine room is leaking excessively, must be replaced. Red tagged, Re-inspection required
|
9/19/2022
|