MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
Machine space stop switch needs repaired or replaced. Only service car in building, needs to be repaired in 10 days or less. Re-inspection required
|
9/5/2024
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
|
|
Post Phase I signage near firefighter's switch.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Category 5 testing needs to be completed, was only able to conduct annual portion of test
|
7/26/2022
|
A17.1-1996 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
102.1
|
|
|
Machine room inspection would not operate as designed. Repair the machine room inspection function as designed.
|
8/10/2020
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch.
|
8/10/2020
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
|
|
Machine room shall not be used for storage
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance control program.
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
1001.2(b)(6)
|
|
|
A ventilation cooling fan located in the elevator controller has failed. The fan shall be replaced as the manufacturer’s design.
|
8/10/2020
|
A17.1-1996 : Elevators
|
3.2 - Car top light and outlet
|
1001.2(c)(2)
|
|
|
NFPA car top outlet has open neutral, repair as needed.
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
206.7
|
x
|
|
Suspension ropes showning sign of rouging and being undersized. Re-inspection is required.
|
4/8/2019
|
A17.1-1996 : Elevators
|
4.5 - Access to Hoistway
|
1001.2(d)(5)
|
|
|
Hoistway access switch on COP is not working. Repair as needed.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean the pit.
|
|