Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) No No Post Phase I signage near firefighter's switch.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code No No The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. 8/10/2020
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) No No A ventilation cooling fan located in the elevator controller has failed. The fan shall be replaced as the manufacturer’s design. 8/10/2020
A17.1-1996 : Elevators 3.2 - Car top light and outlet 1001.2(c)(2) No No NFPA car top outlet has open neutral, repair as needed.
A17.1-1996 : Elevators 4.5 - Access to Hoistway 1001.2(d)(5) No No Hoistway access switch on COP is not working. Repair as needed.
A17.1-1996 : Elevators 4.5 - Access to Hoistway 1001.2(d)(5) No No Hoistway access switch at top landing is not working, needs repaired and test access operation.
A17.1-1996 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 102.1 No No Machine room inspection would not operate as designed. Repair the machine room inspection function as designed. 8/10/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Clean the pit.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide on-site maintenance control program.
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space No No Machine room shall not be used for storage
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Category 5 testing needs to be completed, was only able to conduct annual portion of test 7/26/2022
A17.1-1996 : Elevators 3.23 - Suspension rope 206.7 Yes No Suspension ropes showning sign of rouging and being undersized. Re-inspection is required. 4/8/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Yes No Machine space stop switch needs repaired or replaced. Only service car in building, needs to be repaired in 10 days or less. Re-inspection required 9/5/2024