Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 testing needs to be completed, was only able to conduct annual portion of test 7/26/2022
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) Post Phase I signage near firefighter's switch.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. 8/10/2020
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) A ventilation cooling fan located in the elevator controller has failed. The fan shall be replaced as the manufacturer’s design. 8/10/2020
A17.1-1996 : Elevators 3.2 - Car top light and outlet 1001.2(c)(2) NFPA car top outlet has open neutral, repair as needed.
A17.1-1996 : Elevators 4.5 - Access to Hoistway 1001.2(d)(5) Hoistway access switch on COP is not working. Repair as needed.
A17.1-1996 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 102.1 Machine room inspection would not operate as designed. Repair the machine room inspection function as designed. 8/10/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Clean the pit.
A17.1-1996 : Elevators 3.23 - Suspension rope 206.7 x Suspension ropes showning sign of rouging and being undersized. Re-inspection is required. 4/8/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance control program.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Machine space stop switch needs repaired or replaced. Only service car in building, needs to be repaired in 10 days or less. Re-inspection required 9/5/2024
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Machine room shall not be used for storage