Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.14 - Ventilation 1001.2(a)(14) No No The in cab ventilation fan shall be operational. 1/20/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) Yes No The auxiliary power lowering operation shall be functional. 4/2/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits No No The pit light fixture shall operate as designed. The fixture is full of water and the light is very dim. 4/8/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Water and oil shall not be allowed to accumulate on pit floor. 4/8/2024