Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Need Phase I fire service instructions 11/2/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load recurring every 5 years. 5/9/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Telephone in elevator doesn't work. Phone line dead to elevator controller. 4/30/2020
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The oil pan in the pit is overflowing. The oil needs to be pumped out.
MO Minimum : Elevators (I) - Pits (I)1 The oil pan in the pit is overflowing. The oil needs to be pumped out.