Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.12 - Car enclosure 2.14 The car handrail is missing along with on of the handrail standoffs. This has created a hole exceeding .5" in diameter with nothing in place to prevent a straight through passage beyond the running clearance. This hole shall be permanently covered and a replacement handrail shall be installed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 An MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 1/7/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing The over speed/rupture valve is not sealed. A category 5 test shall be performed on or before the next annual inspection and the over speed/rupture valve shall be sealed. 1/7/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 1/31/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 1/31/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. The fire extinguisher is expired. 4/5/2024