Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) | x | x | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The smoke sensors have been removed from the elevator landings and no signal can be sent to the elevator controller for phase I recall operation. The smoke sensors shall be reinstalled and the devices retested before the elevator shall be returned to service. | 4/9/2019 |