Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Elevator cab ceiling is missing, leaving fluorescent light bulbs unprotected. Either re-install cab ceiling or guard bulbs against breakage.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Elevator cab ceiling is missing leaving fluorescent light bulbs unprotected, Either re-install cab ceiling or guard bulbs against breakage.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts High speed down coil on elevator control valve is not being energized, causing elevator to run at leveling speed in the down direction, needs repaired.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts High speed down coil on elevator control valve is not being energized, causing elevator to run at leveling speed in the down direction, needs to be repaired
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lights in elevator cab do not work, needs repair. Re-inspection required 10/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams x x Water is leaking through drywall ceiling into the elevator controller in machine room causing an unsafe condition. Elevator has been Red-tagged and removed form service. Re-inspection required 10/20/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 2/7/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 x Bottom left hand cylinder needs to be looked at. 4" of rust on the bottom cylinder. 2/7/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current operating certificate shall be on display in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room