Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Access to the machine room shall be clear and unobstructed. Need to remove all items from the stairway leading to the machine room
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed.
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed. 1/13/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned
A17.1-1996 : Elevators 2.17 - Drive machine brake 1002.3d Yes No Faired unintended motion. Rope gripper replacement pads need to be replaced. 2/26/2021
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 102.1 No No Traveling cable jacket has several new breaks at the lobby level, need to repair or replace cable.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No Emergency light not working. 2/26/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 2/29/2024