Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The alarm bell rings constantly, repair so that it operates as intended. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.2 - Stop switches 2.26.2.21 No No The stop switch shall be made operational
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 Yes No 2 of the heat detectors near the machine room and the heat detector at the top of the hoistway shall be made operational. 7/11/2023
A17.1-2016 : Elevators 3.5 - Normal terminal stopping device 3.25.1 Yes No Bottom directional limit switch shall be adjusted. Re-inspection required 10/28/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.12 - Car enclosure 8.11.2.1.1(l) No No Repair damaged hardware (mesh wire) cloth inside elevator cab. 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) No No Provide no passenger sign in car 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) No No Repair car top light. 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.3 - Top-of-car operating device 8.11.2.1.3(c) No No Provide access to the top of car 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.19 - Guide rails fastening and equipment 8.11.2.1.3(y) No No Secure right side rail bracket at 4th floor level. 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) Yes No Provide missing straps on hoistway doors 1/29/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) Yes No Repair door to sill clearance 1st floor. 1/28/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) No No Access means shall be provided at one upper landing to permit access to top of car. 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Written maintenance control program shall be kept on site for each elevator. 12/1/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No OSV due for Cat 5 test 5/4/2022