Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Bottom normal not working properly. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Provide ABC rated fire Extinguisher in machine space 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) Repair car top light. 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) x Repair door to sill clearance 1st and 4th floors. 1/28/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) x Provide missing straps on hoistway doors 1/29/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) Provide hoistway access to the top of car 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) Access means shall be provided at one upper landing to permit access to the top of the car. 12/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator. 12/1/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV is due for Cat 5 testing 5/4/2022
conversion conversion conversion - reinspect x Repair or replace screening on cab wall. 8/20/2018
conversion conversion conversion - reinspect x Secure car top exit. 8/20/2018
conversion conversion conversion - reinspect x Secure car top exit. 10/11/2017
conversion conversion conversion - reinspect x Repair hole in hoistway wall near 4th floor. 10/11/2017
conversion conversion conversion - reinspect x Repair or replace screening on cab wall. 10/11/2017
conversion conversion conversion - reinspect x Refasten back cab wall. 10/11/2017
conversion conversion conversion - reinspect x Repair hole in hoistway wall near 4th floor. 8/20/2018
conversion conversion conversion - reinspect x Refasten back cab wall. 8/20/2018
conversion conversion n/a Provide a permanent source for cab lighting. 12/1/2021
conversion conversion n/a Provide a permanent source of cab lighting. 12/1/2021