Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Need to install guard on car light fixture
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Need to install elevator machine room light, light to supple 10 ft candles minimum illumination
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Install pit light, light shall supply 5 ft candles minimum illumination
MO Minimum : Elevators (I) - Pits (I)7 Install pit stop switch