Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.33 - Compensating ropes and chains 1001.2(c)(30) Yes Yes Replace compensation chain. Spliced at counterweight hitch. Red tagged elevator. 1/30/2021
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) Yes No Governor fails to calibrate to original specifications. Repair/replace and retest. 1/30/2021
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) Yes No Governor fails to calibrate to original specifications. 2/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 2/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed. 1/13/2026
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Hoist ropes are at a minimum diameter, need to replace the ropes within 90 days. Re-inspection required 3/25/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 3/25/2026
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Access to machine room shall be clear and unobstructed. Need to remove all items in stairway leading to the machine room 3/25/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.16 - Traveling cables and junction boxes 2.8.1 No No Traveling cable jacket has unrepaired breaks at the lobby. Need to repair or replace same 3/25/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed. 3/25/2026