Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes are at a minimum diameter, need to replace the ropes within 90 days. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
MO Minimum : Elevators (H) - Machine Rooms (H)1 Access to machine room shall be clear and unobstructed. Need to remove all items in stairway leading to the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.16 - Traveling cables and junction boxes 2.8.1 Traveling cable jacket has unrepaired breaks at the lobby. Need to repair or replace same
MO Minimum : Elevators (H) - Machine Rooms (H)4 The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed.
A17.1-1996 : Elevators 3.33 - Compensating ropes and chains 1001.2(c)(30) x x Replace compensation chain. Spliced at counterweight hitch. Red tagged elevator. 1/30/2021
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) x Governor fails to calibrate to original specifications. Repair/replace and retest. 1/30/2021
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) x Governor fails to calibrate to original specifications. 2/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 2/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed. 1/13/2026