Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Remove the oil from the pit. 6/24/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace the leaking cylinder packing. 6/24/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 Items and materials not related to the function or maintenance of the elevator shall not be stored in the elevator machine room. 11/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers There is no test tag on the fire extinguisher in the machine room. The fire extinguisher shall be properly tagged to indicate the expiration date and type of extinguisher. 11/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/21/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 7/21/2021
MO Minimum : Elevators (I) - Pits (I)1 Remove oil from the pit. The pit shall be kept clean and dry. 7/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Oil is leaking in the pit. Determine the source of the oil leak and take corrective action. 7/21/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing. 8/29/2018
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove all non-elevator related equipment from the machine room. 8/29/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 Provide an ABC type fire extinguisher in the machine room. 8/29/2018
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and dry. Remove fluids from the pit. 8/29/2018
MO Minimum : Elevators (I) - Pits (I)1 Determine the source of fluids in the pit and repair. 8/29/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Cab lights shall be guarded to prevent breakage. 8/29/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking. Door has been removed. Replace door with appropriate fire rated door.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the car top.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Replace damaged/missing door operator belts.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Cab lighting - all lamps shall work.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The existing telephone shall work and call to a number providing 24/7 support. 4/9/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lighting shall be tested and work. No light disconnect in the machine room, nothing labeled as to circuit breaker location.