MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Access to machine room shall be clear and unobstructed. Need to remove all items from the stairway leading to the machine room
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.16 - Traveling cables and junction boxes
|
2.8.1
|
|
|
The car traveling cable, underneath the car, has cracked through the outer insulation as the car reaches the lobby. Confirm that no internal wires have been affected and repair or replace traveling cable.
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
Cables need to be shortened.
|
7/23/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
2/29/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.16 - Traveling cables and junction boxes
|
2.8.1
|
|
|
The car traveling cable, underneath the car, has cracked through the outer insulation as the car reaches the lobby. Confirm that no internal wires have been affected and repair or replace traveling cable.
|
1/13/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed.
|
1/13/2026
|