Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates A sign shall be posted adjacent to hall call fixtures instructing occupants not to use the elevator in case of fire. The sign shall include only the wording and graphics shown in Fig. 2.27.9 of A17.1-2005. 9/24/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The emergency power fixture at the egress floor for this car shall be removed. This car does not operate under emergency power. 5/14/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following testing items still need to be tested to complete the category 5 test: Unintended movement in both directions, set car safeties with full load at contract speed, car buffer shall be compressed with full load at contract speed. 6/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Feeder locations shall be marked on main disconnects and car lighting branch circuit disconnects. 9/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provided feeder locations on main line and 110v disconnects. 8/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.2.1 Machinery and equipment not used in conjunction with the function or use of the elevator shall be removed from the elevator machine room. 9/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/14/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 The penetrations in the hoistway overhead shall be sealed. 9/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Provide all hoistway door upper fire stops to be properly installed. 8/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 8.11.2.1.3(z) Provide governor rope cable data tag. 8/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) Suspension ropes shall have a rope data tag installed. 5/1/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Provide max counterweight runby sign in pit. 8/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate An up-to-date operating certificate is required in the machine room. 5/31/2023