Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency communication in-operable, Re-inspection required 4/5/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Governor rope tail sheave is bottomed out, shorten rope.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Provide pit light to work.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide testing of the elevator emergency power selector switch, located outside of the fire control room. 4/24/2023