MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit is retaining water, need to provide means for water to be removed by the sump pump
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light and alarm bell do not work.
|
12/15/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work on 110V or regular power. Re-inspection required
|
11/16/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Provide current year tested fire extinguisher in the elevator machine room.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Remove water from pit.
|
1/28/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
Fire service key switch is broken from backet at main landing.
|
12/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Clean pit of water and oil. Sump pump
|
2/2/2021
|